ISS-1039 · Northgate Logistics Center · HVAC Equipment & Installation

Ductwork routing conflict with sprinkler main at Grid F-6

IssueMore Info RequestedCriticalDue 2026-08-14Ball in court: Ron Borden
Description

Raised by Tomas Reyes (Evans General Contractors) on 2026-08-06

Coordination model shows the 48x18 supply trunk clashing with the 6" sprinkler main between grids F-5 and F-6. Need a resolution approach before overhead rough-in starts on 8/31.

Response

Proposing a transition to 60x14 for the run between F-5 and F-6 to pass beneath the sprinkler main. Sketch attached.

Ron Borden · 2026-08-11

Comments
Imani Foster, PELowcountry Design Group2026-08-13 08:44

60x14 keeps velocity under 1,800 fpm — acceptable if the transition stays outside 3 duct diameters of the takeoff.

Participants

Tomas Reyes

Requester · Evans General Contractors

Ron Borden

Responder · Apex Mechanical Systems

Imani Foster, PE

Reviewer · Lowcountry Design Group

Status History

Created issue

Tomas Reyes · 2026-08-06 07:55

Submitted response

Ron Borden · 2026-08-11 10:20

Proposed transition to 60x14

Requested more information

Tomas Reyes · 2026-08-12 16:31

Need EOR concurrence on velocity

Attachments

Clash-Report-F6.pdf

640 KB · Tomas Reyes · 2026-08-06

Duct-Transition-Sketch.pdf

412 KB · Ron Borden · 2026-08-11